Article No | EAN | |
---|---|---|
With connection fitting | 9340-00.301 | |
Without connection fitting | 9340-00.302 |
Eclipse HF suitable for manifolds and adjusts the flow rate in the individual heating circuits directly in l/h. This means hydraulic balancing is achieved in one simple operation. The set flow rate is constantly adapted, i.e. if the rate becomes too high, e.g. due to closing adjacent circuits, Eclipse HF controls the flow automatically to the set value. The control cartridge always ensures a constant flow. This makes Eclipse HF a time and cost-saving solution especially for system commissioning.
Heating and cooling systems.
Control
Flow limitation
Shut-off
PN 10
Max. working temperature: 90°C
Min. working temperature: -10°C
The flow can be stepless pre-set within the range: 30-300 l/h.
Delivery setting: Commissioning setting.
Max. 2,5 m3/h per heating circuit manifold.
Max. differential pressure:
60 kPa (<30 dB(A))
Min. differential pressure:
30 – 150 l/h = 17 kPa
150 – 300 l/h = 25 kPa
Thermostatic insert: Brass, PPS (polyphenylsulphide)
O-rings: EPDM
Valve disc: EPDM
Spring: Stainless steel
Spindle: Niro-steel spindle with double O-ring seal. The outer O-ring is replaceable under pressure.
Connection fitting: Nickel-plated brass
HEIMEIER M30x1,5
Article No | EAN | |
---|---|---|
With connection fitting | 9340-00.301 | |
Without connection fitting | 9340-00.302 |
Article No | EAN |
---|---|
9345-00.300 |